Tel : 08451 306 269
email: info@noisestopsystems.co.uk
Armaload Pipe supports are easy to install multi-function pipe supports. Designed to avoid thermal losses by providing an excellent thermal performance at fixing points. Armaload Pipe Supports help to ensure an enclosed insulation system for Air conditioning, light refrigeration and heating installations.
Armaload Pipe Support Sections are a high density, CFC free (ozone depletion potential of zero), flexible elastomeric thermal insulation. It is dark grey in colour and is available in two forms - half round sections to fit over struts, or strips of sheet for floor ducts and cross-overs between banks of pipes.

| Technical Data | ||
| Values | Remarks | |
| Description | High density flexible elastomeric support | |
| Max. Surface Temperature | +105°C | |
| Max. Surface Temperature for Flat Surface | -50°C | |
| Min. Surface Temperature | -30°C | |
| Thermal Conductivity at +20°C | 0.0045 W(m - K) | |
| Water Vapour Permeability | µ 7,000 | |
| Water Absorption | 0.2% by volume | Test acc. to ASTM CS209 |
| Surface Spread of Flame | Class 1 | |
| Reaction to fire | Self-extinguishing, does not drop | |
| Health Aspects | Dust & Fibre Free | |
Outdoor applications should be painted with Armafinish FR paint to the recommended thickness. Two or more coats may be required.
| Armaload Pipe Support | |||||||
| High Density Pipe support | |||||||
| Pipe O.D. mm | 19mm Insulation thickness | ||||||
| Copper Cu | Iron and steel Fe | Min I.D. mm | Max pipe support interval m | Reference | O.D. mm | Width mm | Pcs./carton |
| 15 | 15 | 15 | 2.00 | 34 | 55 | 32 | |
| 22 | 21.3 | 22 | 22 | 2.75 | 41 | 55 | 32 |
| 28 | 26.9 | 28 | 28 | 3.00 | 47 | 55 | 32 |
| 35 | 33.7 | 35 | 35 | 3.50 | 54 | 65 | 32 |
| 42 | 42.4 | 42 | 42 | 3.75 | 61 | 65 | 32 |
| Armaload Pipe Support Section | ||
| Armaload is used as a load bearing insulating insert between insulated pipes and their support in low temperature installations. Where Armaflex is in contact with Armaload some compression of the insulation can be expected, but this will not affect the insulative properties. | ||
| Reference | Description | Carton content m |
| ALOAD-UH | 19mm x 40mm x 1000 mm half-round sections | 40 |